Four initiating zones (expandable to eight) with up to 20 two‑wire smoke detectors per zone
Programmable through keypads or remote programming software (RPS) through a Conettix interface module
Two notification appliance circuits (NACs) on board with a shared internal regulated 24 VFWR, 4 A NAC power supply
Easily converts to addressable with the addition of a MUX expansion module
Reports to two phone numbers, two IP addresses, or a phone number and an IP address
Line impedance for ground fault detection (Option Bus, conventional input, NAC, secondary power circuit, MUX Bus, AUX power, SMK power) | 10kΩ |
Power (Input) | 120V 60Hz 1.4A or 230\240V 50Hz, 0.7A |
Power (Auxiliary) | 17 to 31VFWR, unfiltered, 1.0A |
Power (Smoke)1 | 20.4 to 28.2VDC nominal, filtered, 1.0A. |
Power (Option Bus) | 12VDC nominal, 500mA |
Power (Notification Appliance Circuit [NAC])2 | Each NAC has 24VFWR nominal, unfiltered power with up to 2.5A capacity (but limited by overall 4.0A capacity) |
Power (Optional Standby Batteries) | Two 12V (in series), 7Ah to 40Ah |
NACs Line Impedance (voltage loss) | 1.5V |
Recommended Manufacturers3 | Power Sonic: PS-1270, PS-12170, PS-12180YUASA: NP7-12, NPG18-12 |
1 For compatible smoke detection devices, see also the FPD‑7024 Smoke Detector Compatibility List.2 For compatible NAC devices, see also the FPD‑7024 NAC Compatibility List3 If other manufacturers or battery types are used, ensure that the battery or batteries can handle an initial charge current of at least 1.7 A. | |
Temperature (operating and storage) | +32°F to +120°F (0°C to +49°C) |
Wiring | ClassB or ClassA |
Notification patterns | Configurable for steady, pulsing, California March, Temporal (ANSI) code 3, synchronized Wheelock, synchronized Gentex, and synchronized System Sensor. |
Local (on-board) | The main control panel includes Three FormC relays. The relay contacts are rated at 5A, 28VDC. No over current limiting is performed on the contacts of the relays. The default selection for the relays is to indicate general alarm (relay 1), general system trouble (relay 2), and supervisory (relay 3). By using point or zone mapping, they can be programmed to activate in a wide variety of conditions. |
Remote1 | Eight Form C relay outputs are provided by a D7035 Remote Relay Module. The module connects to the FPD‑7024 through the option bus. The outputs are fully programmable, exactly as the local relays are programmed. Each output operates independently of the other seven to provide complete flexibility. Communication with the D7035 is supervised. Contact Rating: 5A at 28VDCNumber of Modules: two units maximum. |
1 For wiring requirements, see Option bus wiring requirements. | |